  • Search
  • Home
  • Vacon Drives
  • VACON NXP
  • VACON NXP Liquid Cooled Common DC Bus
  • VACON NXP Liquid Cooled Common DC Bus 525-690 V
  • VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 343 kW 525-690V IP00 - 137X0735
  • VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 137X0735
VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 137X0735

VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 343 kW 525-690V IP00 - 137X0735

Send inquiry Order code: 137X0735
(You save )
Brand
VACON
SKU:
137X0735
UPC:
Condition:
New
Series:
VACON NXP Liquid Cooled Common DC Bus
Power (kW):
343
Rated current (A):
325
Mains voltage:
525-690 V
Enclosure:
IP00
Frame size:
CH62
EMC category:
C4
Brake chopper:
No
Control panel:
Alphanumeric Keypad
Type code:
NXA03256-A0T02WG-A1A300D6E3+FL23+MASG+ARFIFF03+DLDE

Adding to cart… The item has been added

Description

The VACON NXP Liquid Cooled Common DC Bus liquid-cooled active front end unit with order code 137X0735 and type code NXA03256-A0T02WG-A1A300D6E3+FL23+MASG+ARFIFF03+DLDE is a 343 kW, three-phase 525-690 V supply, IP00 enclosure, frame CH62 configuration. It is rated 325 A continuous output current and meets EMC category C4.

Key specifications

Order code137X0735
Type codeNXA03256-A0T02WG-A1A300D6E3+FL23+MASG+ARFIFF03+DLDE
SeriesVACON® NXP Liquid Cooled Common DC Bus
Product typeLiquid-Cooled Active Front End Unit
Rated power343 kW
Rated current325 A
Mains voltage525 – 690 Vac (640-1100 Vdc)
PhasesThree phase
EnclosureIP00
Frame sizeCH62
EMC categoryC4
Brake chopperNot included
Control panelAlphanumeric Keypad
Standard I/O6DI,DO,2AI,1AO,+10Vr,+24V
Dimensions (H x W x D)658 x 246 x 374 mm
Net weight55 kg
EAN5715253793535

Type code configuration

OptionCodeSelection
Product GroupNXAActive Front-End Unit
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationWLiquid cooling
Mains voltage6-525 – 690 Vac (640-1100 Vdc)
Current0325325 Amp
Control KeypadAAlpha-numeric display
Enclosure0IP00
EMC emission levelsTIEC61800-3 for IT networks
Brake Chopper0No Brake
Electrical Modification2AFE module w/o LCL
Card ModificationsG-FiberConnection+Varnished PCB
Shipping Package+GSCBCardboard box as Shipping pack
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGNONo conduit plate
Option Slot AA16DI,DO,2AI,1AO,+10Vr,+24V
Option Slot BA31RO(NO/NC),1RO(NC), therm
Option Slot C00No board
Option Slot DD6CAN-MonBus galv.decoupled
Option Slot EE3PROFIBUS DP
Firmware language package+FL23UK,NL,DE,FR,ITWestEurII
Documentation Level+DPAPPaper manuals
Documentation Lang. Preference+DLDEGerman
System Firmware+FNP02System software NXP
Software license+MASGGrid Converter license
Application+ARFIFF03Grid Converter NXA,NXI,NXP
Parameter SetNONEnone
Motor Parameter Default+LS50Default Motor frequency 50HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeCH62Frame 62 liquid cooled
Motor Power Low Overload [kW]343343
Motor Power High Overload [kW]--
Dimensions WxHxD [mm]246X658X374246X658X374
Continuous Current (NO) [A]295295
Continuous Current (HO) [A]--
customized ID+BM26+BM26

Typical applications

At 343 kW, this liquid-cooled active front end unit is typically used for compact high-power multi-drive systems in marine, offshore and process industry.

Configuration notes

  • An active front-end (AFE) unit feeds the common DC bus from the mains and returns braking energy to the grid, with low harmonic distortion.
  • IP00 is an open module for mounting inside a cabinet or switchgear.
  • EMC category C4 has no internal RFI filter and is intended for IT (ungrounded) networks or installations with an external filter.
  • It is supplied with an alphanumeric keypad for local control and parameter setting.
  • Installed option boards: slot A: 6DI,DO,2AI,1AO,+10Vr,+24V; slot B: 1RO(NO/NC),1RO(NC), therm; slot D: CAN-MonBus galv.decoupled; slot E: PROFIBUS DP.

About the VACON NXP Liquid Cooled Common DC Bus series

VACON® NXP Liquid Cooled Common DC Bus modules combine liquid cooling with a shared DC bus for compact, high-power multi-drive systems up to several megawatts in marine, offshore and process industry.

Need this exact configuration or an alternative? Send us the order code 137X0735 or the type code and we will help you find the right drive.

  • Related Products
VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 137U6163

VACON 

VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 343 kW 525-690V IP00 - 137U6163

The VACON NXP Liquid Cooled Common DC Bus liquid-cooled active front end unit with order code 137U6163 and type code NXA03256-A0T02WG-A1A2D700E9+ARFIFF03 is a 343 kW, three-phase 525-690 V supply,...
VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 137L5401

VACON 

VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 343 kW 525-690V IP00 - 137L5401

The VACON NXP Liquid Cooled Common DC Bus liquid-cooled active front end unit with order code 137L5401 and type code NXA03258-A0T02WG-A100000000+ARFIFF05 is a 343 kW, three-phase 525-690 V supply,...
VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 137L1058

VACON 

VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 343 kW 525-690V IP00 - 137L1058

The VACON NXP Liquid Cooled Common DC Bus liquid-cooled active front end unit with order code 137L1058 and type code NXA03256-A0T02WG-A100000000+MASG+ARFIFF03 is a 343 kW, three-phase 525-690 V...
VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 136Z9767

VACON 

VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 343 kW 525-690V IP00 - 136Z9767

The VACON NXP Liquid Cooled Common DC Bus liquid-cooled active front end unit with order code 136Z9767 and type code NXA03256-A0T02WG-A1AFD7B2E6+FL23+GRID+ARFIF106+DLDE is a 343 kW, three-phase...
VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 137U9653

VACON 

VACON NXP Liquid Cooled Common DC Bus Liquid-Cooled Active Front End Unit 343 kW 525-690V IP00 - 137U9653

The VACON NXP Liquid Cooled Common DC Bus liquid-cooled active front end unit with order code 137U9653 and type code NXA03258-A0T02WG-A8A2B500E9+GSNT+SPXE is a 343 kW, three-phase 525-690 V supply,...