VACON NXP Grid Converter Inverter Unit 110 kW 380-500V IP00 - 137N1175
- Brand
- VACON
- SKU:
- 137N1175
- Condition:
- New
- Series:
- VACON NXP Grid Converter
- Power (kW):
- 110
- Rated current (A):
- 205
- Mains voltage:
- 380-500 V
- Enclosure:
- IP00
- Frame size:
- FI09
- EMC category:
- C4
- Brake chopper:
- No
- Control panel:
- Alphanumeric Keypad
- Type code:
- NXI02055-A0T0ISG-A8A2D7E200+MASG+ARFIFF03+DLCN+GACS
Description
The VACON NXP Grid Converter inverter unit with order code 137N1175 and type code NXI02055-A0T0ISG-A8A2D7E200+MASG+ARFIFF03+DLCN+GACS is a 110 kW, three-phase 380-500 V supply, IP00 enclosure, frame FI09 configuration. It is rated 205 A continuous output current and meets EMC category C4.
Key specifications
| Order code | 137N1175 |
|---|---|
| Type code | NXI02055-A0T0ISG-A8A2D7E200+MASG+ARFIFF03+DLCN+GACS |
| Series | VACON® NXP Grid Converter |
| Product type | Inverter Unit |
| Rated power | 110 kW |
| Power, high overload | 90 kW |
| Rated current | 205 A |
| Current, high overload | 170 A |
| Mains voltage | 380 – 500 Vac (465-800 Vdc) |
| Enclosure | IP00 |
| Frame size | FI09 |
| EMC category | C4 |
| Brake chopper | Not included |
| Control panel | Alphanumeric Keypad |
| Standard I/O | OPTA1 w.galv.isol 2AI&1AO |
| Dimensions (H x W x D) | 1030 x 239 x 372 mm |
| Net weight | 67 kg |
| EAN | 5715253589237 |
Type code configuration
| Option | Code | Selection |
|---|---|---|
| Product Group | NXI | NXI Inverter Unit |
| Customized Drive | +BM26 | Vacon Dark Grey NXP |
| Mechanical Modification | S | Standard air cooled drive |
| Mains voltage | 5- | 380 – 500 Vac (465-800 Vdc) |
| Current | 0205 | 205 Amp |
| Control Keypad | A | Alpha-numeric display |
| Enclosure | 0 | IP00 |
| EMC emission levels | T | IEC61800-3 for IT networks |
| Brake Chopper | 0 | No Brake |
| Electrical Modification | I | INU, no charging circuit |
| Card Modifications | G- | FiberConnection+Varnished PCB |
| Shipping Package | +GSCB | Cardboard box as Shipping pack |
| Warranty | +WT01 | Warranty 12/18 months |
| Gland Plate Option | +QGNO | No conduit plate |
| Option Slot A | A8 | OPTA1 w.galv.isol 2AI&1AO |
| Option Slot B | A2 | 2RO(NO/NC) |
| Option Slot C | D7 | Line voltage meas. |
| Option Slot D | E2 | RS485 (Modbus/N2) |
| Option Slot E | 00 | No board |
| Firmware language package | +FL22 | UK,FR,IT,ES,PT;WestEur |
| Documentation Level | +DPAP | Paper manuals |
| Documentation Lang. Preference | +DLCN | Chinese |
| System Firmware | +FNP02 | System software NXP |
| Software license | +MASG | Grid Converter license |
| Application | +ARFIFF03 | Grid Converter NXA,NXI,NXP |
| Parameter Set | NONE | none |
| Motor Parameter Default | +LS50 | Default Motor frequency 50HZ |
| Labeling options | +LPC1 | no additional labels |
| CE Approval | +GACE | CE Approval |
| UL Approval | +GAUL | UL approval |
| RCM Approval | +GACT | RCM Approval N16307 |
| Marine approval | +GACS | China Classification Society |
| KC Approval | +GAKC | Korean Approval |
| Ukrainian Approval | +GAUA | Ukrainian Approval |
| EAC Approval | +GAEA | EAC Approval |
| Frame Size | FI09 | Frame 09 INU |
| Motor Power Low Overload [kW] | 110 | 110 |
| Motor Power High Overload [kW] | 90 | 90 |
| Dimensions WxHxD [mm] | 239X1030X372 | 239X1030X372 |
| Continuous Current (NO) [A] | 205 | 205 |
| Continuous Current (HO) [A] | 170 | 170 |
Typical applications
At 110 kW, this inverter unit is typically used for shore power, micro-grids, renewable energy and hybrid marine power systems.
Configuration notes
- An inverter unit (INU) takes power from the common DC bus and controls the motor or converts DC to AC.
- IP00 is an open module for mounting inside a cabinet or switchgear.
- EMC category C4 has no internal RFI filter and is intended for IT (ungrounded) networks or installations with an external filter.
- For heavy-duty use with high overload the rating is 90 kW / 170 A.
- It is supplied with an alphanumeric keypad for local control and parameter setting.
- Installed option boards: slot A: OPTA1 w.galv.isol 2AI&1AO; slot B: 2RO(NO/NC); slot C: Line voltage meas.; slot D: RS485 (Modbus/N2).
About the VACON NXP Grid Converter series
VACON® NXP Grid Converters connect generators, energy storage and renewable sources to the grid or to an island network. They control voltage and frequency, support shore connection and micro-grids, and keep harmonic distortion low.
Need this exact configuration or an alternative? Send us the order code 137N1175 or the type code and we will help you find the right drive.