Series:
VACON NXP Common DC Bus
Power (kW):
22
Rated current (A):
45
Mains voltage:
380-500 V
Enclosure:
IP21
Frame size:
FR06
EMC category:
C4
Brake chopper:
No
Control panel:
Alphanumeric Keypad
Type code:
NXB00455-A2T08SV-A1A2000000

Adding to cart… The item has been added

Description

The VACON NXP Common DC Bus brake chopper unit with order code 136G0153 and type code NXB00455-A2T08SV-A1A2000000 is a 22 kW, three-phase 380-500 V supply, IP21 enclosure, frame FR06 configuration. It is rated 45 A continuous output current and meets EMC category C4.

Key specifications

Order code136G0153
Type codeNXB00455-A2T08SV-A1A2000000
SeriesVACON® NXP Common DC Bus
Product typeBrake Chopper Unit
Rated power22 kW
Power, high overload18.5 kW
Rated current45 A
Current, high overload38 A
Mains voltage380 – 500 Vac (465-800 Vdc)
EnclosureIP21/NEMA1
Frame sizeFR06
EMC categoryC4
Brake chopperNot included
Control panelAlphanumeric Keypad
Standard I/O6DI,DO,2AI,1AO,+10Vr,+24V
Dimensions (H x W x D)519 x 195 x 237 mm
Net weight18.5 kg
EAN5710108565886

Type code configuration

OptionCodeSelection
Product GroupNXBBrake Chopper Unit
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationSStandard air cooled drive
Mains voltage5-380 – 500 Vac (465-800 Vdc)
Current004545 Amp
Control KeypadAAlpha-numeric display
Enclosure2IP21/NEMA1
EMC emission levelsTIEC61800-3 for IT networks
Brake Chopper0No Brake
Electrical Modification8BCU Brake chopper unit
Card ModificationsV-DirectConn. w Varnished Boards
Shipping Package+GSCBCardboard box as Shipping pack
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGLCInch conduit plate
Option Slot AA16DI,DO,2AI,1AO,+10Vr,+24V
Option Slot BA22RO(NO/NC)
Option Slot C00No board
Option Slot D00No board
Option Slot E00No board
Firmware language package+FL22UK,FR,IT,ES,PT;WestEur
Documentation Level+DPAPPaper manuals
Documentation Lang. Preference+DLUKEnglish
System Firmware+FNP02System software NXP
Software licenseNONEno software license
Application+ABFIFF01Brake Chopper Unit NXB
Parameter SetNONEnone
Motor Parameter Default+LS50Default Motor frequency 50HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeFR06Frame 06
Motor Power Low Overload [kW]2222
Motor Power High Overload [kW]18.518.5
Dimensions WxHxD [mm]195X519X237195X519X237
Continuous Current (NO) [A]4646
Continuous Current (HO) [A]3838

Typical applications

At 22 kW, this brake chopper unit is typically used for multi-drive systems that share one DC bus, such as paper machines, cranes, test benches and process lines.

Configuration notes

  • A brake chopper unit dissipates excess DC bus energy in an external braking resistor during braking.
  • IP21 / UL Type 1 suits clean indoor electrical rooms.
  • EMC category C4 has no internal RFI filter and is intended for IT (ungrounded) networks or installations with an external filter.
  • For heavy-duty use with high overload the rating is 18.5 kW / 38 A.
  • It is supplied with an alphanumeric keypad for local control and parameter setting.
  • Installed option boards: slot A: 6DI,DO,2AI,1AO,+10Vr,+24V; slot B: 2RO(NO/NC).

About the VACON NXP Common DC Bus series

VACON® NXP Common DC Bus modules (active front-end, rectifier, brake chopper and inverter units) build multi-drive systems that share one DC bus. Braking energy is reused between drives or fed back to the grid, reducing energy cost and cabinet size.

Need this exact configuration or an alternative? Send us the order code 136G0153 or the type code and we will help you find the right drive.

  • Related Products
VACON NXP Common DC Bus Brake Chopper Unit 132H6246

VACON 

VACON NXP Common DC Bus Brake Chopper Unit 2 kW 380-500V IP21 - 132H6246

The VACON NXP Common DC Bus brake chopper unit with order code 132H6246 and type code NXB00315-A2T08SV-A1A20000E6+QGLM is a 2 kW, three-phase 380-500 V supply, IP21 enclosure, frame FR06...
VACON NXP Common DC Bus Brake Chopper Unit 132L1532

VACON 

VACON NXP Common DC Bus Brake Chopper Unit 2 kW 380-500V IP21 - 132L1532

The VACON NXP Common DC Bus brake chopper unit with order code 132L1532 and type code NXB00455-A2T08SV-A1A20000E9+QGLM+FL23+DLDE is a 2 kW, three-phase 380-500 V supply, IP21 enclosure, frame FR06...
VACON NXP Common DC Bus Brake Chopper Unit 132L2526

VACON 

VACON NXP Common DC Bus Brake Chopper Unit 2 kW 380-500V IP21 - 132L2526

The VACON NXP Common DC Bus brake chopper unit with order code 132L2526 and type code NXB00165-A2T08SV-A1A2000000 is a 2 kW, three-phase 380-500 V supply, IP21 enclosure, frame FR06 configuration. It...
VACON NXP Common DC Bus Brake Chopper Unit 132L4080

VACON 

VACON NXP Common DC Bus Brake Chopper Unit 2 kW 380-500V IP21 - 132L4080

The VACON NXP Common DC Bus brake chopper unit with order code 132L4080 and type code NXB00725-A2T08SV-A1A20000E6+QGLM+DLNL is a 2 kW, three-phase 380-500 V supply, IP21 enclosure, frame FR07...
VACON NXP Common DC Bus Brake Chopper Unit 137N2399

VACON 

VACON NXP Common DC Bus Brake Chopper Unit 2 kW 380-500V IP21 - 137N2399

The VACON NXP Common DC Bus brake chopper unit with order code 137N2399 and type code NXB00095-A2T08SV-A1A20000E9 is a 2 kW, three-phase 380-500 V supply, IP21 enclosure, frame FR04 configuration. It...