  • Search
  • Home
  • Vacon Drives
  • VACON NXP
  • VACON NXP Air Cooled 525-690 V
  • VACON NXP Air Cooled AC Drive 30 kW 525-690V IP54 - 137U5894
  • VACON NXP Air Cooled AC Drive 137U5894
VACON NXP Air Cooled AC Drive 137U5894

VACON NXP Air Cooled AC Drive 30 kW 525-690V IP54 - 137U5894

Send inquiry Order code: 137U5894
(You save )
Brand
VACON
SKU:
137U5894
UPC:
Condition:
New
Series:
VACON NXP Air Cooled
Power (kW):
30
Rated current (A):
34
Mains voltage:
525-690 V
Enclosure:
IP54
Frame size:
FR06
EMC category:
C3
Brake chopper:
No
Control panel:
Alphanumeric Keypad
Type code:
NXP00346-A5L0SSV-0000000000

Adding to cart… The item has been added

Description

The VACON NXP Air Cooled AC Drive with order code 137U5894 and type code NXP00346-A5L0SSV-0000000000 is a 30 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR06 configuration. It is rated 34 A continuous output current and meets EMC category C3.

Key specifications

Order code137U5894
Type codeNXP00346-A5L0SSV-0000000000
SeriesVACON® NXP Air Cooled
Product typeAC Drive
Rated power30 kW
Power, high overload22 kW
Rated current34 A
Current, high overload27 A
Mains voltage525 – 690 Vac (640-1100 Vdc)
PhasesThree phase
EnclosureIP54/NEMA12
Frame sizeFR06
EMC categoryC3
RFI filterClass A2
Brake chopperNot included
Control panelAlphanumeric Keypad
Standard I/ONo board
Dimensions (H x W x D)557 x 195 x 237 mm
Net weight18.5 kg
EAN5715253743523

Type code configuration

OptionCodeSelection
Product GroupNXPNXP Frequency Converter
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationSStandard air cooled drive
Mains voltage6-525 – 690 Vac (640-1100 Vdc)
Current003434 Amp
Control KeypadAAlpha-numeric display
Enclosure5IP54/NEMA12
EMC emission levelsLIEC61800-3, 2. environment
Brake Chopper0No Brake
Electrical ModificationS6-pulse with choke
Card ModificationsV-DirectConn. w Varnished Boards
Shipping Package+GSCBCardboard box as Shipping pack
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGLCInch conduit plate
Option Slot A00No board
Option Slot B00No board
Option Slot C00No board
Option Slot D00No board
Option Slot E00No board
Firmware language package+FL22UK,FR,IT,ES,PT;WestEur
Documentation Level+DQCKQuick guide user manual
Documentation Lang. Preference+DLUKEnglish
System Firmware+FNP02System software NXP
Software licenseNONEno software license
Application+A000No Special Application
Parameter SetNONEnone
Motor Parameter Default+LS50Default Motor frequency 50HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeFR06Frame 06
Motor Power Low Overload [kW]3030
Motor Power High Overload [kW]2222
Dimensions WxHxD [mm]195X557X237195X557X237
Continuous Current (NO) [A]3434
Continuous Current (HO) [A]2727

Typical applications

At 30 kW, this AC Drive is typically used for cranes, hoists, winches, extruders, test benches and paper and steel process lines.

Configuration notes

  • IP54 / UL Type 12 protects against dust and splashing water for mounting directly in production areas.
  • EMC category C3 is intended for industrial (second environment) networks.
  • There is no integrated brake chopper; for fast braking use an external braking unit or a regenerative solution.
  • For heavy-duty use with high overload the rating is 22 kW / 27 A.
  • It is supplied with an alphanumeric keypad for local control and parameter setting.

About the VACON NXP Air Cooled series

VACON® NXP is a high-performance air-cooled AC drive for demanding industrial applications such as cranes, winders, marine and process lines. It provides accurate open- and closed-loop motor control, five option-board slots for I/O, encoders and fieldbuses, and configurable application software.

Need this exact configuration or an alternative? Send us the order code 137U5894 or the type code and we will help you find the right drive.

  • Related Products
VACON NXP Air Cooled AC Drive 137G3577

VACON 

VACON NXP Air Cooled AC Drive 30 kW 525-690V IP54 - 137G3577

The VACON NXP Air Cooled AC Drive with order code 137G3577 and type code NXP00346-A5T0SSV-A8A2000000+QGLM is a 30 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR06 configuration. It is...
VACON NXP Air Cooled AC Drive 137H2447

VACON 

VACON NXP Air Cooled AC Drive 30 kW 525-690V IP54 - 137H2447

The VACON NXP Air Cooled AC Drive with order code 137H2447 and type code NXP00346-A5T1SSV-A1AF0000E9+QGLM is a 30 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR06 configuration. It is...
VACON NXP Air Cooled AC Drive 136H5800

VACON 

VACON NXP Air Cooled AC Drive 30 kW 525-690V IP54 - 136H5800

The VACON NXP Air Cooled AC Drive with order code 136H5800 and type code NXP00346-A5L1SSV-A1AFA5B1E9+QGLM is a 30 kW (40 HP), three-phase 525-690 V supply, IP54 enclosure, frame FR06 configuration...
VACON NXP Air Cooled AC Drive 136Z6784

VACON 

VACON NXP Air Cooled AC Drive 30 kW 525-690V IP54 - 136Z6784

The VACON NXP Air Cooled AC Drive with order code 136Z6784 and type code NXP00346-A5T1SSV-A1A2000000+QGLM+FL21+DNOT is a 30 kW (40 HP), three-phase 525-690 V supply, IP54 enclosure, frame FR06...
VACON NXP Air Cooled AC Drive 137X2198

VACON 

VACON NXP Air Cooled AC Drive 30 kW 525-690V IP54 - 137X2198

The VACON NXP Air Cooled AC Drive with order code 137X2198 and type code NXP00346-A5L1SSV-A1A3000000+QGLM+FL23+LS60+DPAP+DLDE is a 30 kW (40 HP), three-phase 525-690 V supply, IP54 enclosure, frame...