VACON NXP Air Cooled AC Drive 137H2839

VACON NXP Air Cooled AC Drive 160 kW 525-690V IP54 - 137H2839

Send inquiry Order code: 137H2839
(You save )
Brand
VACON
SKU:
137H2839
UPC:
Condition:
New
Series:
VACON NXP Air Cooled
Power (kW):
160
Rated current (A):
170
Mains voltage:
525-690 V
Enclosure:
IP54
Frame size:
FR09
EMC category:
C4
Brake chopper:
No
Control panel:
Alphanumeric Keypad
Type code:
NXP01706-A5T0SSG-A8AFBHBHE9

Adding to cart… The item has been added

Description

The VACON NXP Air Cooled AC Drive with order code 137H2839 and type code NXP01706-A5T0SSG-A8AFBHBHE9 is a 160 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR09 configuration. It is rated 170 A continuous output current and meets EMC category C4.

Key specifications

Order code137H2839
Type codeNXP01706-A5T0SSG-A8AFBHBHE9
SeriesVACON® NXP Air Cooled
Product typeAC Drive
Rated power160 kW
Power, high overload132 kW
Rated current170 A
Current, high overload144 A
Mains voltage525 – 690 Vac (640-1100 Vdc)
PhasesThree phase
EnclosureIP54/NEMA12
Frame sizeFR09
EMC categoryC4
Brake chopperNot included
Control panelAlphanumeric Keypad
Standard I/OOPTA1 w.galv.isol 2AI&1AO
Dimensions (H x W x D)1150 x 480 x 362 mm
Net weight146 kg
EAN5715253394558

Type code configuration

OptionCodeSelection
Product GroupNXPNXP Frequency Converter
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationSStandard air cooled drive
Mains voltage6-525 – 690 Vac (640-1100 Vdc)
Current0170170 Amp
Control KeypadAAlpha-numeric display
Enclosure5IP54/NEMA12
EMC emission levelsTIEC61800-3 for IT networks
Brake Chopper0No Brake
Electrical ModificationS6-pulse with choke
Card ModificationsG-FiberConnection+Varnished PCB
Shipping Package+GSCBCardboard box as Shipping pack
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGLCInch conduit plate
Option Slot AA8OPTA1 w.galv.isol 2AI&1AO
Option Slot BAFSTO, ATEX therm
Option Slot CBH3 temp meas channels
Option Slot DBH3 temp meas channels
Option Slot EE92-port ethernet
Firmware language package+FL22UK,FR,IT,ES,PT;WestEur
Documentation Level+DQCKQuick guide user manual
Documentation Lang. Preference+DLUKEnglish
System Firmware+FNP02System software NXP
Software licenseNONEno software license
Application+A000No Special Application
Parameter SetNONEnone
Motor Parameter Default+LS50Default Motor frequency 50HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeFR09Frame 09
Motor Power Low Overload [kW]160160
Motor Power High Overload [kW]132132
Dimensions WxHxD [mm]480X1150X362480X1150X362
Continuous Current (NO) [A]170170
Continuous Current (HO) [A]144144
ATEX Marking 1ATEX: II (2) GDATEX: II (2) GD

Typical applications

At 160 kW, this AC Drive is typically used for cranes, winders, paper machines, rolling mills, marine and offshore applications.

Configuration notes

  • IP54 / UL Type 12 protects against dust and splashing water for mounting directly in production areas.
  • EMC category C4 has no internal RFI filter and is intended for IT (ungrounded) networks or installations with an external filter.
  • There is no integrated brake chopper; for fast braking use an external braking unit or a regenerative solution.
  • For heavy-duty use with high overload the rating is 132 kW / 144 A.
  • It is supplied with an alphanumeric keypad for local control and parameter setting.
  • Installed option boards: slot A: OPTA1 w.galv.isol 2AI&1AO; slot B: STO, ATEX therm; slot C: 3 temp meas channels; slot D: 3 temp meas channels; slot E: 2-port ethernet.

About the VACON NXP Air Cooled series

VACON® NXP is a high-performance air-cooled AC drive for demanding industrial applications such as cranes, winders, marine and process lines. It provides accurate open- and closed-loop motor control, five option-board slots for I/O, encoders and fieldbuses, and configurable application software.

Need this exact configuration or an alternative? Send us the order code 137H2839 or the type code and we will help you find the right drive.

  • Related Products
VACON NXP Air Cooled AC Drive 132H7004

VACON 

VACON NXP Air Cooled AC Drive 160 kW 525-690V IP54 - 132H7004

The VACON NXP Air Cooled AC Drive with order code 132H7004 and type code NXP01706-A5T0SSG-A1AF0000E9+QGLM+FL24+DPAP+DLCZ is a 160 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR09...
VACON NXP Air Cooled AC Drive 132N1342

VACON 

VACON NXP Air Cooled AC Drive 160 kW 525-690V IP54 - 132N1342

The VACON NXP Air Cooled AC Drive with order code 132N1342 and type code NXP01706-A5T0SSG-A1A2B20000+QGLM is a 160 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR09 configuration. It is...
VACON NXP Air Cooled AC Drive 137L7082

VACON 

VACON NXP Air Cooled AC Drive 160 kW 525-690V IP54 - 137L7082

The VACON NXP Air Cooled AC Drive with order code 137L7082 and type code NXP01706-A5T0SSG-A1A3000000+QGLM+FL23+DPAP+DLDE is a 160 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR09...
VACON NXP Air Cooled AC Drive 132X5789

VACON 

VACON NXP Air Cooled AC Drive 160 kW 525-690V IP54 - 132X5789

The VACON NXP Air Cooled AC Drive with order code 132X5789 and type code NXP01706-A5T0SSG-A1A2BH00E9+DCD3+ADFIF101+GADN+LPC2 is a 160 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR09...
VACON NXP Air Cooled AC Drive 137L4066

VACON 

VACON NXP Air Cooled AC Drive 160 kW 525-690V IP54 - 137L4066

The VACON NXP Air Cooled AC Drive with order code 137L4066 and type code NXP01706-A5L1SSG-A1A300CP00+QGLM+FL21+DLDK is a 160 kW, three-phase 525-690 V supply, IP54 enclosure, frame FR09 configuration...